We are major producer of dry type transformer and power distribution transformers. Dry type power transformer, lets trouble-free performance and low power loss while operation. Get quality Dry type transformer with standard fittings (electronic atomatic voltage regulator, bi-directional rollers, lifting lugs, etc.) and also provide optional accessories on request.
We are able to comply with most international and customer specifications
| Sr.No | Rating | Overall Dimentions | Total Weight | %z | ||
|---|---|---|---|---|---|---|
| KVA | Length(L) | Breath(B) | Height(H) | in Kgs. | % | |
| 1. | 1000 | 2730 | 2080 | 2285 | 4300 | 5.0 |
| 2. | 1250 | 2730 | 2080 | 2285 | 5900 | 5.0 |
| 3. | 1500 | 2730 | 2080 | 2285 | 6100 | 6.25 |
| 4. | 2000 | 2800 | 2500 | 2550 | 7000 | 6.25 |
| 5. | 2500 | 2850 | 2650 | 2750 | 8200 | 6.25 |
| N.B |
|
|||||
1) Magnetic circuit - Lamination CRGO M3 to M5, MOH and ZDKH type
2) Electric circuit - Electrolytic grade 99.9% pure copper with transposition in L.V. coil for current sharing in parallel conductors
3) Dielectric circuits - Electric grade Nomex paper and fibre glass components
4) Thermal circuit - Effective cooling by natural air through axial and radial ducts
Specific Features1) Designed for trouble-free performance
2) Design conforms to IS 2026, IS 11171 and other international standards
3) Low power loss and low noise
4) Designed to withstand electrical impulses and thermal and dynamic stresses
Optimum utilization of active materials for compactness5) Modern manufacturing techniques ensure cost effectiveness, reliability and a long trouble-free performance
6) Compact design, hence consumes less floor area. Best suited for in-door installation
7) Can be installed very close to the load thereby saving expensive L.T. cable. This avoids voltage drop and power loss
8) Averts fire and prevents it from spreading
Specifications1) 3 phase, 50 Hz 11kv
2) Range 200KVA-2500KVA Class
3) Class F/H insulated
4) Vector group Dyn 11
5) Continuous duty
6) Copper wound as per relevant standards
7) HV side cable boxes
8) LV side busduct
9) Paintings as per IS-5 specification
Standard Fittings1) Rating & Diagram plate
2) Jacking lugs
3) Lifting lugs
4) Air insulated on load tap charger
5) Remote tap charger control cubide
6) Electronic Automatic Voltage Regulator
7) IP 23 Enclosure
8) Winding temperature scanner with alarm and trip contact
9) P.T 100 sensor each limb
10) Bi-directional rollers
11) HV Terminal Board & Epoxy Terminals
12) Air insulated HV Cable Box Top Entry
13) Bottom Entry on request
14) LV Bus Duct with Copper Bus Bars
15) Suitable for local & remote operations
Optional Accessories on requestNeutral C.T.
Annunciation Window